  • This control zooms the charts that have a date axis. Totals are for the full record.
utility out reconnect hold, computed

17 interruptions in 24 months

  • Each mark is one time the house went to battery. Its height is how long it stayed there.
  • The pale part of every mark is the five minutes the inverter must wait once the grid is back.
  • So only the solid part is the time the utility was out.
  • 9 of these marks have no solid part at all.

No grid failure ends before the five-minute hold, to within 3 seconds

  • IEEE 1547 clause 4.10 sets an Enter Service delay: the inverter watches five minutes of healthy grid before it reconnects.
  • New York's Department of Public Service publishes 300 s as the required default.
  • The floor shows without a label. The shortest grid failure lasted 299.9 seconds.
  • That is within the 3 seconds of jitter the gateway's edges carry.
  • Only the single intentional off-grid test is below it. No anti-islanding rule governs that test.

When they happen

  • Hour of the day runs across, and month runs down.
  • A run is failures that each began within 3 hours of the one before.
  • A run of two came within 9 minutes, from 14:22 on 13 May 2026.
  • A run of three came within 61 minutes, from 15:54 on 2 July 2026.
  • A run of two came within 6 minutes, from 02:30 on 6 July 2026.
  • A run of two came within 43 minutes, from 23:20 on 13 August 2026.

What the weather was doing

  • Every hour on record is a pale dot. The hours that hold an outage are marked.
  • Hover for each one's rank against hours from the same fortnight and time of day. A rank against all hours would only say that July afternoons are warm.
  • The two failures from 13 May 2026 began at 67 and 67°F, with gusts of 4 and 6 mph.
  • The three failures from 2 July 2026 began at 93, 89 and 88°F, with gusts of 0, 1 and 4 mph.
  • The two failures from 6 July 2026 began at 70 and 70°F, with gusts of 0 and 0 mph.
  • The highest gust against comparable hours came on 4 April 2026: 10 mph, at 57°F.
  • That gust is at or above 98% of hours from the same fortnight and time of day.
  • A percentile says an hour was unusual for the season, not that conditions were extreme. The dashed lines mark absolute thresholds.
  • The station is in the garden, so this is the weather at my house, not at an airport.
grid solar battery house

Each one, close up

  • Twenty minutes either side: each trace shows that much time before and after its outage.
  • Grid power drops to exactly zero and then stops being written at all.
  • Home Assistant records on change, and a steady value produces no rows.
  • The gap in the line is the outage. The battery supplies the house throughout.